Data centers & critical infrastructure / UAE

Data Center Solutions

Plan the physical infrastructure for a new data center, server room or facility upgrade. MMC UAE helps coordinate racks, critical power, cooling and monitoring so the design reflects how the facility will operate.

Data center design and installation for the operating load

A data center project should begin with a load schedule, not an empty room and a rack count. Two rooms containing the same number of cabinets can need very different electrical distribution and cooling. MMC UAE scopes the physical infrastructure around the equipment you intend to operate, the services that must remain available and the next stage of growth. New server rooms, occupied-room upgrades and phased facility builds each need a different delivery sequence.

Our starting point is a survey of the proposed space and existing infrastructure. Record clear room dimensions, slab and access constraints, supply availability, cooling routes, drainage and the path from unloading to final equipment position. Establish who controls each interface: landlord, consultant, electrical contractor, network team and facilities operator. That responsibility schedule prevents equipment arriving before the site can accept it.

Coordinate racks, power and cooling before procurement

The design scope connects cabinet layout, rack density, aisle access, cable routes and equipment service space. Electrical planning covers the critical load, redundancy objective, UPS topology, maintenance bypass and downstream distribution. Thermal planning follows the heat from server intake to final rejection outside the building. Monitoring should expose the conditions an operator can act on, rather than simply collecting every available reading.

MMC can coordinate an ATTOM equipment proposal covering integrated micro data centers, modular infrastructure, precision cooling, critical power and DCIM. The bill of materials should identify selected models, options, quantities and the assumptions behind sizing. Separate the equipment supply from builders’ work, utility alterations and specialist installation activities so the quotation is usable by the complete project team.

Supply, installation, commissioning and AMC

After design review, agree the procurement release, delivery checks and site readiness milestones. Installation activities can include cabinet positioning, infrastructure assembly, equipment interconnections and monitoring configuration within the contracted boundary. Electrical and mechanical work must follow the approved site design and agreed contractor responsibilities. A live facility also needs a migration method, rollback trigger and permitted interruption window.

Commissioning demonstrates the agreed design intent. Check equipment start-up, rack power identification, cooling response, sensor readings and alarm routing. Where authorised and practical, test the response to the specified failure scenarios. Record results, outstanding defects and acceptance owners. Handover should include the equipment register, as-built layouts, configuration records, warranty information and operating instructions. An annual maintenance contract can then define inspection tasks, consumables, access arrangements and escalation; attendance times and spare holdings need explicit agreement.

Designing for UAE buildings and climate

Dubai and Abu Dhabi installations need a design basis that reflects the actual site. Check summer design ambient at the selected condenser position, exposure to dust, service access and the effect of rooftop routing. Indoor conditions also matter: tenant fit-outs can restrict plant locations, available electrical capacity and out-of-hours access. These constraints may change which architecture is feasible before any equipment rating becomes relevant.

For phased projects, reserve expansion paths rather than installing empty capacity without a use plan. Identify which additional racks can be energized without modifying occupied aisles and which future cooling connections can be isolated. Keep the facility resilience objective separate from a certification claim. Supplying redundant equipment alone does not establish a certified data center tier or a guaranteed availability figure.

A reference to guide the discussion

ATTOM’s CPPA manufacturer story illustrates the role of containment, cable management and monitoring in organising a facility. Use the case study section to explore that application, then assess the design against your own room. It is a manufacturer reference, not an MMC customer installation claim.

For a quotation, provide the rack schedule with expected and peak loads, current drawings, redundancy requirements, utility information and target handover date. If measurements are missing, make the survey a first project milestone. This service page concerns site design, installation and maintenance; the linked product pages describe equipment configurations and supply options.

Equipment for this service

Service scope

What we can help you plan

Rack and capacity planning

Estimate the initial rack count and power density, with room for growth.

Power and thermal coordination

Review distribution, UPS, cooling and equipment clearances together.

Operations and expansion

Define what the team needs to monitor and where more capacity can be added.

Next steps

Explore related services

Project locations

Planning a project in Dubai or Abu Dhabi?

A little more clarity

Frequently asked questions

Useful answers to help you plan your next step.

Discuss your requirements ↗
Can MMC upgrade a data center while it remains occupied?

The scope must define live equipment, temporary arrangements, migration batches, permitted interruptions and rollback criteria. A survey establishes which work can proceed without taking systems offline.

What is included in data center commissioning?

Agree checks for power identification, equipment start-up, cooling response, environmental readings, alarm delivery and authorised failure scenarios. The acceptance record should name the responsible reviewer.

Does redundant equipment make a facility Tier certified?

No. Facility certification involves the complete design and its applicable assessment process. Redundancy in a product schedule is only one input.

What should a data center AMC cover?

Specify the asset list, inspection tasks, consumables, reporting, site access and escalation. Response windows, emergency attendance and spare parts must be stated in the contract.

Talk to MMC UAE

Tell us about your project.

Share your requirements so we can discuss the right next step for your site.

14th Floor, Tamani Arts Building, Business Bay, Dubai

Send an enquiry

Data Center Solutions


    Phone number